Mobile water quality systems ready to ship — CALL TODAY 800.748.2322

VERDA Water Quality Systems
Cattle standing in a stream illustrating the upstream and downstream risks behind SPD water reliability

The symptom is not always the failure

Let me start with a familiar maintenance story. An SPD is having washer problems. Instruments are coming out with residue. Staff are frustrated. Maintenance gets called. The first response makes sense: Check the washer. So the machine is inspected. Chemistry gets reviewed. Settings are adjusted. Staff practices may even be revisited. Sometimes that solves it. Sometimes it doesn’t.

And when it doesn’t, that is usually the moment when the investigation has to change. Instead of asking: “What equipment is acting up?” we need to ask: “What function is failing, and what failure mode could be causing it?” That is the shift reliability-centered maintenance asks us to make.

There’s an old cowboy philosophy attributed to Will Rogers that fits: “Always drink upstream from the herd“. The cowboy may only see the water at the point where he takes a drink, but the quality problem may have started farther upstream. SPD water works the same way. The visible symptom may appear at the washer, on the instrument, or in a test result, while the underlying failure mode is developing elsewhere in the water system. Reliability-centered maintenance teaches us to look upstream, trace the condition to its source, and address the cause before the downstream consequence gets worse.


Start with the job, not the asset

Clayton Christensen’s “Jobs to Be Done” thinking offers a useful parallel. He asked: “Why don’t we organize ourself around a job to be done?” That question fits Facilities surprisingly well. We can become overly focused on the washer, softener, RO skid, or filter because those are the assets in front of us. But the job is not simply to keep an RO system running. The job is to reliably provide water of the quality needed to support medical-device processing. Once the job is defined correctly, the investigation changes. That is also how ASHE frames reliability-centered maintenance. RCM starts by defining the true function of a system or asset, then evaluates its risk and criticality to facility operations.


The symptom is often downstream

Sterile Processing usually sees the consequence first. They may see: spotting, residue, staining, corrosion, inconsistent washer performance, or unusual water-quality results. But the failure may be somewhere else. In another hospital case Len Sparks has used to illustrate root-cause investigation, an SPD struggled with persistent washer performance issues. The washer was adjusted. Chemistry was changed. Staff practice was reviewed. Yet the problem kept coming back.

Eventually, the team looked upstream. The reverse-osmosis system had been drifting in performance for months, but the available data had not made that drift obvious. The washer was where the problem showed up. The water system was where the problem was developing. That is a critical distinction.


Consider this hospital example

A hospital in the Southeast U.S. experienced a similar pattern earlier this year. Their sterile processing team was seeing unusually rapid degradation of sterilizers, cart washers, and plumbing components. Repeated failures eventually led the team to open components and inspect what was happening inside.

They found significant corrosion and scaling. Independent testing then identified poor water quality, including elevated silica and other contaminants, as a contributor. More than 20 of the 33 contaminants tested exceeded ST108 limits, and silica approached 33 mg/L.

At first glance, the problem looked like a collection of equipment failures. But the deeper issue was systemic. The sterilizer was not the whole problem. The cart washer was not the whole problem. The plumbing was not the whole problem. Those assets were showing the effects of a broader water-quality failure mode.

That changes how maintenance should respond.

This is why root-cause thinking matters. If Facilities keeps repairing the visible asset without correcting the upstream condition, the organization may continue treating the consequence instead of the cause. This hospital’s own experience supports that lesson. The hospital reported nearly 100 repair orders for water leaks in autoclave sterilizers since 2018, along with repeated replacement of corroded piping, valves, and fittings. That is not just a maintenance history. It is evidence!

And evidence should change the investigation.


Functional failure can happen before equipment stops

One of the most useful concepts in RCM is functional failure. A system can still be running and yet fail to perform the function the hospital depends on. For SPD water, that means: water still flows, pumps still run, valves still open, and equipment still appears operational. But the water quality may no longer be consistently supporting the processing function. That is why “running” is not the same as “reliable.”


The first lesson

The first lesson from reliability-centered maintenance is simple: Do not confuse the symptom with the failure.

Ask:

  • What function are we trying to protect?
  • What would failure of that function look like?
  • What failure modes could produce the symptom we are seeing?
  • Are we investigating the whole system, or just the asset where the symptom appeared?

That shift alone can save enormous time. Because the visible problem may be in SPD but the failure may have started somewhere upstream.

What comes next

Once you identify the real failure mode, a second question appears: What should we do about it?

That is where Part 2 begins. Not every failure mode deserves the same maintenance strategy. The next step is deciding which failures should be prevented on a schedule, which should be monitored for condition, which require predictive intervention, and which can reasonably be allowed to fail.

Consultation Request - Talk With an Expert

Name(Required)
Email(Required)
Facility Type

Address(Required)